Sprint 2000
A hand held combustion analyser measuring CO and O2, CO2 (calculated), CO/CO2 ratio, sample temperature, combustion efficiency, gauge and differential pressure, CO alarm, data logging, infrared data link (to PC and printer) and rechargeable battery pack, all supplied in a soft carrying case. To assist in ensuring gas safety, and to realise the higher efficiencies available from new appliance technologies, proper installation set up and servicing is essential. Sprint 2000 provides easy combustion testing with less need for boiler strip down, increasing overall operational efficiency.
Sprint 2000 Specification
Instrument:
Range: -10º to 50ºC
Battery: rechargeable Ni-MH. Life >6 hours
Charger input voltage: 115V or 230V; 50/60 Hz AC
Fuels: natural gas, LPG, light oil, heavy oil, + other (specified)
Display: backlit LCD
Header: customer programmable
Data logging: 25 sets of readings
Time and date: 24 hour clock
Dimensions: 500g
Casing: rubber case (option)
Conforms to: BS7927
Probes:
Standard efficiency probe
Construction: pistol grip; 250mm probe length; 2500mm hose length
K-type thermocouple: Accuracy +/-0.3%; +/-1ºC
Maximum temperature: 800ºC
Combined air/surface/liquid probe (option)
Usage: Room, radiator and tap water temperatures
Temperature range: -50ºC to 400ºC
Gases: | Range | Resolution | Accuracy |
Oxygen | 0 – 25% | 0.1% | +/-0.3% |
Carbon monoxide | 0 – 10,000ppm | +/- 1ppm | <100ppm; +/- 5ppm |
Carbon dioxide (calculated) | 0 – 25% | ||
CO/CO2 ratio | 0 – 0.9999 | ||
Combustion efficiency | 0 – 100% | ||
Gas leak sensor (option) | 20 – 10,000ppm |
Draught/pressure measurement:
Range: +/-25%
Resolution: 0.01mbar
Accuracy: +/-0.5% fsd
Apex Instruments, 125 Quantum Street, Box 727, Holly Springs, NC 27540. Tel: 919-557-7300; Fax: 919-557-7110.